- ZoneMaster Series
- ZoneMaster provides total facility protection by stopping surge voltages on AC power
- before they enter your building.
|
|
ZoneMaster 300 is engineered to protect critical electronic systems from severe transient environments, providing decades of uninterrupted surge protection. A tested surge capacity of 300,000A assures a high level of protection from even the most severe lightning strikes. |
|
ZoneMaster 150 is designed to withstand the severe transient environment at large service entrance panels. 150,000A of independently tested surge capacity assures a high level of protection from severe lightning strikes. |
|
ZoneSentinel is specifically tailored for applications at distribution boards and small service entrance locations. When used at a local panel, in combination with a ZoneMaster at the service entrance, ZoneSentinel provides the lowest surge suppression voltages available today. |
ZoneMaster 300 Features: |
- 300,000A surge capacity per phase
- Replaceable modules
- Full protection redundancy
- Module diagnostics
- Color coded modules
- Remote indication capabilities
- Blocks lightning induced transient voltages at the main service panel
- 50% smaller than other devices with similar capacity
- NO/NC dry contacts for remote monitoring
- NEMA 1, 2, 3, 3S, 4, 4X, 12, 13 rated enclosure
- Ultra low impedance construction
- Thermal and short circuit fusing
- Five Year Warranty
- >Patented Technology (No. 5,311,393)
|
Electrical Specifications |
Maximum Surge Current Capacity per Phase: |
|
300,000A (8/20µs) |
Maximum Surge Current Capacity: |
L-N |
300,000A (8/20µs) |
|
L-L |
300,000A (8/20µs) |
|
N-G |
75,000A (8/20µs) |
Duty Cycle Performance: |
200,000A (8/20µs) |
>4 Impulses |
(Surge Life) |
10,000A (8/20µs) |
>3,500 Impulses |
|
200A (8/20µs) |
infinite |
Maximum Continuous Operating Voltage: |
|
25% above nomina |
Remote Indication Contacts: |
|
NO/NC 125VAC 2A rated |
Module Diagnostics: |
Protection Present |
Green LED |
|
Fault warning |
Mechanical (fuse link operated) flag |
|
High Voltage neutral to ground |
Red LED |
Protection Technology: |
|
Patented large block, three terminal MOV |
Module Protection: |
|
UL94-5V rated plastic enclosure |
ZoneMaster 150 Features: |
- 150,000A surge capacity per phase
- Replaceable modules
- Comprehensive diagnostics
- Remote indication capabilities
- NO/NC dry contacts for remote monitoringNEMA 1, 2, 3, 3S, 4, 4X, 12, 13 rated enclosure
- Protection redundancy ensures reliability for critical lines
- Low impedance construction
- High N/G voltage warning
- Dual thermal and short circuit fusing
- Color coded modules
- Five Year - No fuss warranty
- Patented Technology (No. 5,311,393)
|
Electrical Specifications |
Maximum Surge Current Capacity per Phase: |
|
150,000A (8/20µs) |
Maximum Surge Current Capacity: |
L-N |
150,000A (8/20µs) |
|
L-L |
150,000A (8/20µs) |
|
N-G |
75,000A (8/20µs) |
Duty Cycle Performance: |
100,000A (8/20µs) |
>4 Impulses |
(Surge Life) |
10,000A (8/20µs) |
>2,500 Impulses |
|
150A (8/20µs) |
infinite |
Maximum Continuous Operating Voltage: |
|
25% above nominal |
Remote Indication Contacts: |
|
NO/NC 125VAC 2A rated |
Module Diagnostics: |
Protection Present |
Green LED |
|
Fault warning |
Mechanical (fuse link operated) flag |
|
High Voltage neutral to ground |
Red LED |
Protection Technology: |
|
Patented large block, three terminal MOV |
Module Protection: |
|
Dual thermal and short circuit fusing mechanisms, UL94-5V rated plastic enclosure |
ZoneSentinel Features: |
- 90,000A per phase (tested capacity)
- Modular Construction
- Remote indication
- NO/NC dry contacts for remote monitoring
- Replaceable modules
- Protects all equipment supplied from the same distribution board
- Assures protection to 90,000A of surge current in a small package
- NEMA 1, 2, 3, 3S, 4, 4X, 12, 13 rated enclosure
- Low impedance construction
- High N/G voltage warning
- TEN mode protection
- Five Year - No fuss warranty
- Patented Technology (No. 5,311,393)
|
Electrical Specifications |
Maximum Surge Current Capacity per Phase: |
|
90,000A (8/20µs) |
Maximum Surge Current Capacity: |
L-N |
45,000A (8/20µs) |
|
L-L |
45,000A (8/20µs) |
|
L-G |
45,000A (8/20µs) |
|
N-G |
45,000A (8/20µs) |
Duty Cycle Performance: |
45,000A (8/20µs) |
>4 Impulses |
(Surge Life) |
10,000A (8/20µs) |
>1,500 Impulses |
|
100A (8/20µs) |
infinite |
Maximum Continuous Operating Voltage: |
|
25% above nominal |
Remote Indication Contacts: |
|
NO/NC 125VAC 2A rated |
Module Diagnostics: |
Protection Present |
Green LED |
|
Fault warning |
Mechanical (fuse link operated) flag |
|
High Voltage neutral to ground |
Red LED |
Protection Technology: |
|
Patented large block, three terminal MOV |
Module Protection: |
|
Dual thermal and short circuit fusing mechanisms, UL94-5V rated plastic enclosure |
|
|